Connect-Tek USB-8 Instrucciones de operaciones Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
11 / 16
EN-TraceTekTTTS12-IM-H8085601/15
THERMAL BUILDING &
INDUSTRIAL HEAT TRACING SOLUTIONS
6. Optional Additional Relay Connections
a. TTSIM-1A units have a built in Form-C alarm relay that can be configured to indicate LEAK; LEAK or TROUBLE; or LEAK,
SERVICE NEEDED or TROUBLE. The access to these individual relays is via Terminals 10,11 and 12 on each installed
TTSIM-1A unit, see below.
b. The ADAM-4069 module has 8 relays. The first three of these are pre-assigned for buzzer control, summary LEAK and
summary TROUBLE. The fourth relay is a watchdog contact that switches to the alarm position if the ADAM-4069 fails to
detect communications activity on the RS-485 external device buss. (Lack of activity indicates loss of power or a frozen
computer).
The remaining 4 relays are available as user programmable relays (see H80760 Operation Manual for set-up options and
details). Physical connections to the relays are made at the ADAM-4069 module
i. Remove the ADAM-4522 by loosening two screws and temporarily disconnecting the RS232 connector.
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16

Comentarios a estos manuales

Sin comentarios