The ON-OFF control may introduce excessive process oscillation
even if hysteresis is minimized to the smallest. If ON-OFF con-
trol is set (i.e., PB1=0), TI1, TD1, CYC1, OFST, CPB and PL1
will be hidden and have no function to the system. The manual
mode, auto-tuning, self-tuning and bumpless transfer will be dis-
abled too.
Heat only P ( or PD ) control:
Select REVR for OUT1, set TI1 to 0,
SP1 is used to adjust set point value,
TIME is used to adjust the dwell timer
(enabled by selecting TIMR for A1FN
or A2FN). OFST been enabled in case
of TI1=0 is used to adjust the control
offset (manual reset). Adjust CYC1
according to the output 1 type (O1TY).
Generally, CYC1=0.5~2 seconds for
SSRD and SSR, CYC1=10~20 seconds
for relay output. CYC1 is ignored if lin-
ear output is selected for O1TY. O1HY
is hidden if PB1 is not equal to 0.
OFST Function: OFST is measured by % with range
0–100.0%. In the steady state (i.e., process has been stabilized),
if the process value is lower than the set point a definite value, say
5°C, while 20°C is used for PB1, that is lower 25%, then increase
OFST 25%, and vice versa. After adjusting OFST value, the
process value will be varied and eventually coincide with set
point. Using the P control (TI1 set to 0), the auto-tuning and self-
tuning are disabled. Refer to section 3-21 “manual tuning” for the
adjustment of PB1 and TD1. Manual reset (adjust OFST) is not
practical because the load may change from time to time and
often need to adjust OFST repeatedly.
The PID control can avoid this situation.
Heat only PID control: Selecting
REVR for OUT1, SP1 is used to adjust
set point value. TIME is used to adjust
the dwell timer (enabled by selecting
TIMR for A1FN or A2FN). PB1 and TI1
should not be zero. Adjust CYC1
according to the output 1 type (O1TY).
Generally, CYC1=0.5~2 seconds for
SSRD and SSR, CYC1=10~20 seconds
for relay output. CYC1 is ignored if lin-
ear output is selected for O1TY. In most
cases, self-tuning can be used to substi-
tute for auto-tuning. See section 3-19. If
self-tuning is not used (select NONE for
SELF), then use auto-tuning for the new
process, or set PB1, TI1, and TD1 with
historical values. See section 3-20 for
auto-tuning operation. If the control
result is still unsatisfactory, then use
manual tuning to improve control. See
section 3-21 for manual tuning. TEC-
9300 contains a very clever PID and
Fuzzy algorithm to achieve a very small
overshoot and very quick response to
the process if it is properly tuned.
3–4 Heat Only Control continued…
Setup P:
OUT1 =
TI1 = 0
CYC1 (if RELAY,
SSRD or SSR is
selected for
O1TY)
Adjust:
SP1, OFST, TIME
(if enabled),
PB1(0), TD1
Setup PID:
OUT1 =
O1TY
CYC1 if RELAY,
SSRD or SSR is
selected for O1TY)
SELF=NONE or
YES
Adjust:
SP1, TIME (if
enabled), PB1(0),
TI1(0), Td1
Auto-tuning:
Used for new
process during ini-
tial tuning
Self-tuning:
Used for a process
any time.
Manual Tuning:
May be used if
self-tuning and
auto-tuning are
inadequate.
3–5 Cool Only Control
ON-OFF control, P (PD) control,
and PID control can be used for
cool control. Set OUT1 to DIRT
(direct action). The other func-
tions for cool only ON-OFF control, cool only P (PD) control and
cool only PID control are the same as the descriptions in section
3-5 for heat only control except that the output variable (and
action) for the cool control is inverse to the heat control, such as
the following diagram shows:
Refer to section 3-5, in which similar descriptions for heat only
control can be applied to cool only control.
Setup Cool Control: