Example
Communications
Alarm 1
Output 2 / Alarm 2
Output 1
Signal Input
Power Input
4: 90 - 264 VAC, 50/60 HZ
5: 11 - 26 VAC or VDC
9: Special Order
0: None
1: RS-485
2: RS-232
3: Retransmit 4-20mA/0-20mA
4: Retransmit 1 - 5V / 0 - 5V
5: Retransmit 0 - 10V
9: Special order
1: Standard Input
Input 1 - Universal Input
Thermocouple: J, K, T, E, B,
R, S, N, L
RTD: PT100 DIN, PT100 JIS
Current: 4 - 20mA, 0 - 20 mA.
Voltage: 0 - 1V, 0 - 5V, 1 - 5V,
0 - 10V
Input 2 - CT and Analog Input
***
CT: 0 - 50 Amp. AC Current
Transformer
Analog Input: 4 - 20 mA,
0 - 20mA, 0 - 1V, 0 - 5V,
1 - 5V, 0 - 10V.
Input 3 - Event Input ( EI )
9: Special Order
1: Relay rated 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V/30mA
3: Isolated
4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac Output
1A / 240VAC, SSR
C: Pulsed voltage to
drive SSR, 14V/40mA
9: Special order
9: Special order
2A / 240VAC
2: Form B Relay
2A / 240VAC
1: Form A Relay
0: None
12
34
5
6
0: None
1: Form A Relay 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac Output, 1A / 240VAC, SSR
7: Isolated 20V / 25mA DC
Output Power Supply
8: Isolated 12V / 40 mA DC
Output Power Supply
9: Isolated 5V / 80mA DC
Output Power Supply
TEC-9300-411111
90 - 264 operating voltage
Input: Standard Input
Output 1: Relay
Output 2: Relay
Alarm 1: Form A Relay
RS-485 Communication Interface
Range set by front keyboard
Alternative between RS-232 and EI
Need to order an accessory TEC99999 if
Heater Break detection is required.
TEC-9300-
***
**
*
*
*
*
**
**
*
*
*
C: Pulsed voltage to
drive SSR, 14V/40mA
A: Special order
Comentarios a estos manuales